Affordable Housing Association of Nova Scotia · Affordable Housing / Deep Energy Retrofit

From Sunset Terrace to Affordable Housing

81%
Energy Reduction
81%
GHG Reduction
12
Affordable Units Created
135
Year-Old Building Preserved
01

The challenge

Sunset Terrace, vacant since 2020

Old Ladies' Home, Yarmouth, N.S. — vintage postcard
Sunset Terrace, c. 1900

Built in 1890 as the Old Ladies’ Home Society, the building at 8 James Street in Yarmouth — known for over a century as “Sunset Terrace” — has been vacant since 2020. The Affordable Housing Association of Nova Scotia (AHANS) is purchasing it and converting it from 21 dormitory-style rooms into 12 modern apartments, funded through CMHC’s Canada Greener Affordable Housing (CGAH) program and the Province of Nova Scotia Department of Growth and Development. Acceptance requires a deep energy retrofit achieving at least 70% energy and 80% greenhouse gas reductions.

BEA conducted the energy audit and modelling study to support the application.

02

The baseline

A building with no energy history

Because the building has stood empty since 2020, there was no historical energy consumption to anchor the analysis — the utility record a retrofit application normally rests on simply did not exist. BEA proposed, and CMHC approved, a modelled baseline: the existing building envelope and mechanical systems paired with the projected occupancy of 12 apartment units.

That baseline is what the site assessment documented. The three-storey Victorian residence encloses over 3,200 m³ of volume, heated by a single oil-fired cast-iron boiler estimated at 65% efficiency, distributing heat through cast-iron radiators. There is no ventilation system, no cooling, and no programmable controls.

Space Heating
76% of energy use
Heating System
Oil boiler
Ventilation
None
Annual Energy Cost
$41k/year
GHG Emissions
72.5 t CO₂e/year

8 James Street, Yarmouth, NS

03

The approach

Thousands of combinations, three finalists

Using Volta SNAP, BEA performed parametric modelling, evaluating thousands of unique upgrade combinations against that baseline. Each package was assessed for whole-building energy and GHG reductions against the CGAH program targets, then ranked by capital cost. The three top-performing packages were presented to AHANS, who selected the preferred option:

Envelope

3.5" spray foam cathedral ceiling, walls insulated to a nominal R-31 (final assembly TBD), double/argon/vinyl windows, insulated steel doors, and ~75% air leakage reduction.

Heating

95% AFUE condensing propane boiler for primary heat, plus 12 mini-split heat pumps (HSPF-IV=15, SEER=38) — one per unit for supplemental heating and cooling.

Hot Water & Ventilation

0.95 UEF condensing propane instantaneous water heater. 12 dedicated 75% SRE heat recovery ventilators — one per unit.

Controls & Water

12 mini-split smart thermostats for individual unit control. Low-flow showerheads and faucet aerators throughout.

04

The results

81% less energy, 81% less carbon

Before After Change
Energy 996 GJ/yr 184 GJ/yr −81%
GHG Emissions 72.5 t CO₂e/yr 13.6 t CO₂e/yr −81%
Operating Cost $40,672/yr $9,161/yr −78%

The preferred upgrade package meets both CGAH program targets — 81% energy reduction against a 70% target, and 81% GHG reduction against an 80% target. The energy reduction is straightforward; the GHG target is the harder one, as GHG reductions are very challenging in Nova Scotia due to its current grid intensity.

05

Beyond energy

Twelve apartments, and another century

This project is not just an energy retrofit. It will create 12 affordable housing units in a community where none existed — converting dormitory rooms with half bathrooms into one- and two-bedroom apartments with full kitchens and bathrooms.

The building envelope improvements and new HRVs in every unit will provide controlled ventilation and improved indoor air quality. Mini-split heat pumps give tenants individual temperature control and cooling for the first time. New windows and air sealing will reduce noise from the surrounding streets.

At 135 years old, 8 James Street has deep roots in Yarmouth. This retrofit preserves that heritage while extending the building’s useful life for decades to come.

Energy AuditingEnergy ModellingDeep Energy RetrofitsBuilding Science
Prepared by
For AHANS
← All case studies